2026/06/11
Upgraded Broken Furnace to Heat Pump System, Upgraded Misterhouse Compatible Thermostats from HAI RC-80/RC-90 to Omnistat2 RC-1000/RC-2000, and Debugged Bad Signalling to Honeywell Home HZ322 Zone Board
π
2026-06-11 01:01
in Linuxha
Old furnace eventually burnt a hole in itself and started leaking burnt gas, which trigger an overtemp protection and shut down the entire unit:
What was interesting is that the W1/heat signal was getting there, but not the Y1/cool or Fan signals. After taking my thermostat on the bench with a separate 24VAC power supply and a multimeter to make sure the outputs were working, I confirmed they were, so the thermostat was fine. But the moment I plugged it back to the wall, it was not, and I even confirmed that I couldn't see 24VAC signals on the thermostat2 input on the zone board. So I spliced the signals on the thermostat to measure them when it was plugged into the wall, and confirmed the signals weren't coming out for fan or cool, even though I could even hear the relay flip. That was super puzzling. Then it took a lot of head scratching, until I finally found this with my multimeter, pin #1 aka RC (circled in blue) didn't have power even though it was jumpered to RH which did have 24VAC power.
obviously once I noticed that tightened it, RC started getting power, Y1 and G started sending 28VAC output, and now the signals are reaching the zone board and everything works. Took 2H to diagnose end to end, though. Do I get a partial refund from the installer for finishing the job? :) (I'm actually curious how long it would have taken them to find this, it was pretty non obvious) And obligatory dilbert cartoon :) And now, the misterhouse HAI/Omnistat code I wrote for multiple thermostats works fine, and it properly supports RC-1000/RC-2000 thanks to others who contributed that code earlier on:
![]()
the AC still worked, but it was obsolete design and freon, worth replacing with the heat pump
![]()
new heat exchanger (AC that works in both directions)
![]()
so I was able to use 'conventional mode'
![]()
all nice and setup, testing stage 2 cooling (2 arrows next to cool)
![]()
zone board acknowledging stage 2 and sending it to furnace
What was interesting is that the W1/heat signal was getting there, but not the Y1/cool or Fan signals. After taking my thermostat on the bench with a separate 24VAC power supply and a multimeter to make sure the outputs were working, I confirmed they were, so the thermostat was fine. But the moment I plugged it back to the wall, it was not, and I even confirmed that I couldn't see 24VAC signals on the thermostat2 input on the zone board. So I spliced the signals on the thermostat to measure them when it was plugged into the wall, and confirmed the signals weren't coming out for fan or cool, even though I could even hear the relay flip. That was super puzzling. Then it took a lot of head scratching, until I finally found this with my multimeter, pin #1 aka RC (circled in blue) didn't have power even though it was jumpered to RH which did have 24VAC power.
![]()
allowing testing signals while the RC-1000 is plugged in
![]()
easy to test the output, and I confirmed I got no output for fan or cooling
![]()
and then I saw this, the jumper from 2 (RH) to 1 (RC) was installed, but the screw was not tightened, so it didn't touch
obviously once I noticed that tightened it, RC started getting power, Y1 and G started sending 28VAC output, and now the signals are reaching the zone board and everything works. Took 2H to diagnose end to end, though. Do I get a partial refund from the installer for finishing the job? :) (I'm actually curious how long it would have taken them to find this, it was pretty non obvious) And obligatory dilbert cartoon :) And now, the misterhouse HAI/Omnistat code I wrote for multiple thermostats works fine, and it properly supports RC-1000/RC-2000 thanks to others who contributed that code earlier on: